Niagara QNX Patches - HAREMB-1220/1221
Problem:
|
Solution:
Installing the patched files for the affected versions will remedy the issue.
Installation Instructions
Archive the files at the bottom of this article. These contains folders for Niagara Ax 3.8 update 4 (r38), Niagara 4.4 update 3 (r44) and, Niagara 4.7 update 1 (r47).
- Unzip the zip archive into a temporary working folder.
- Make sure you have the corresponding version of Niagara Workbench installed.
- Copy the dist files from the folder (r38, r44 or r47) for that release into:
- <niagara_user_home> \ sw \ inbox
Note: <niagara_user_home> in N4 is your windows profile user folder \ Niagara4.x \<brandId>
Example:
C:\users\myUserName\Niagara4.7\tridium\sw\inbox
Note: In Ax the niagara_user_home is the location where you installed.
Example:
C:\Niagara\Niagara-3.8.401\sw\inbox
- Restart the version of Workbench you are updating.
- Connect to the platform of the device
- Open the Software Manager
- Observe the files are no longer in the inbox of the user home
- Commission the device using the “Commissioning Wizard”
- Make sure the “install/upgrade core software from distribution files” box is checked
- Confirm the version number of the dists being installed
Product | QNX Patches |
---|---|
Niagara AX 3.8u4 | OS Dist: 2.7.402.2 NRE Config Dist: 3.8.401.1 |
Niagara 4.4u3 | OS Dist: 4.4.73.38.1 NRE Config Dist: 4.4.94.14.1 |
Niagara 4.7u1 | OS Dist: (JACE 8000) 4.7.109.16.1 NRE Config Dist: 4.7.110.32.1 |