Distech ECB/ECL Series Controllers – Wiring Best Practices

Distech ECB/ECL Series Controllers – Wiring Best Practices

Product(s) Affected:

ECB Series Controllers (200, 300, 400, 600 Series)
ECL Series Controllers (200, 300, 400, 600 Series)

Summary:

If the controllers were wired while whole and excessive torque was used, the terminal block tray can shift left and right causing the pin which is fixed and very solid to the face of the controller, to push on the left and right leads in the terminal strip.  In effect this widens the gap, causing feathered connections.

More Information:

See the attached Application Note "MISC020 - ECB-ECL Series Terminal Connectors.pdf" below for more information and details.  Pass this along to your installers / electricians who do your wiring to make sure you don't continue to have problems.

Questions?:

If you have any questions or concerns please feel free to reach out to our Technical Support group at techsupport@activelogix.com


Related content

Distech Fall '18 Releases including EC-Net Release N4.7 - (4.7.109.20.3)
Distech Fall '18 Releases including EC-Net Release N4.7 - (4.7.109.20.3)
More like this
Technical Bulletin: Updated JACE 3, 6, 7 & 8000 Cleaning & Conversion Processes to Address Niagara 4.1 2021 Date Issue
Technical Bulletin: Updated JACE 3, 6, 7 & 8000 Cleaning & Conversion Processes to Address Niagara 4.1 2021 Date Issue
More like this
Distech EC-Net Release N4.6 - (4.6.96.28)
Distech EC-Net Release N4.6 - (4.6.96.28)
More like this
Distech EC-Net Update Releases for AX (3.8.401) and N4 (4.4.92)
Distech EC-Net Update Releases for AX (3.8.401) and N4 (4.4.92)
More like this
Honeywell - Niagara 4.6
Honeywell - Niagara 4.6
More like this
Vykon - Niagara 4.6
Vykon - Niagara 4.6
More like this